Skip to content
Español

FREE JHA TEMPLATE

Hot work job hazard analysis (JHA) template

Hot work, such as welding, cutting, brazing or grinding, throws sparks that can travel and start fires far from the work. OSHA's general industry rule requires the authorizing person to inspect the area first, preferably with a written permit (29 CFR 1910.252(a)(2)(iv)), and fire watchers where more than a minor fire could develop. Plan fire control before you start.

JHA template

Hot work

StepHazardControls
1. Decide if hot work is really neededSpark-producing work in a place with fire…Use a cold method such as mechanical cutting, clamps…
2. Get the permit and walk the areaHazards are missed before the torch is litHave the authorizing person inspect the area and set…
3. Clear and protect combustiblesSparks reach wood, paper, insulation or…Relocate combustibles at least 35 feet from the work…

The task

Cutting, welding or grinding in an occupied building or work area, with a permit, area clearing, fire watch and a check after the work is done.

Steps, hazards and controls

Controls run from most effective to least. A citation beside a control means an OSHA paragraph requires it; with no citation it is good practice.

StepHazardControls
1. Decide if hot work is really neededSpark-producing work in a place with fire exposures
  1. Eliminate: Use a cold method such as mechanical cutting, clamps or bolted joints instead of heat where the job allows.
  2. Substitute: Move the object to a designated hot work area when practical. (29 CFR 1926.352(a))
  3. Administrative control: Do not cut or weld where explosive atmospheres exist or may develop, such as in uncleaned tanks or where combustible dust builds up. (29 CFR 1910.252(a)(2)(vi)(C))
2. Get the permit and walk the areaHazards are missed before the torch is lit
  1. Administrative control: Have the authorizing person inspect the area and set the precautions, preferably in a written permit. (29 CFR 1910.252(a)(2)(iv))
  2. Administrative control: List every trade in the area and tell them hot work is starting.
  3. Administrative control: Check the area for flammable paint, vapors or dust before work begins. (29 CFR 1926.352(c))
3. Clear and protect combustiblesSparks reach wood, paper, insulation or fluids
  1. Eliminate: Relocate combustibles at least 35 feet from the work site where practicable. (29 CFR 1910.252(a)(2)(vii))
  2. Engineering control: Shield what cannot move with flameproofed covers, metal guards or curtains. (29 CFR 1910.252(a)(2)(vii))
  3. Engineering control: Confine heat, sparks and slag and protect immovable fire hazards. (29 CFR 1926.352(b))
  4. Administrative control: Where paper, wood shavings or other combustibles are on the floor, sweep it clean for a radius of 35 feet. (29 CFR 1910.252(a)(2)(v))
Sparks escape through openings
  1. Engineering control: Protect or shut down ducts and conveyor systems that could carry sparks to distant combustibles. As good practice, also close floor and wall openings near the work. (29 CFR 1910.252(a)(2)(viii))
  2. Administrative control: Check the opposite side of walls, floors and ceilings where heat can transfer. (29 CFR 1926.352(f))
4. Position fire watch and extinguishersSmall fire not caught right away
  1. Administrative control: Station a fire watcher where other than a minor fire could develop, including where appreciable combustibles are closer than 35 feet. (29 CFR 1910.252(a)(2)(iii)(A))
  2. Administrative control: Train fire watchers in extinguisher use and give them a way to sound an alarm. (29 CFR 1910.252(a)(2)(iii)(B))
  3. Administrative control: Keep suitable fire extinguishing equipment ready for instant use. (29 CFR 1926.352(d))
5. Do the hot workIgnition from spatter, torch leaks or grinding sparks
  1. Engineering control: Shut off the torch gas supply outside any enclosed space when the torch is not in use. (29 CFR 1926.352(g))
  2. Administrative control: Stop work if conditions change, such as a gas smell or an alarm.
  3. PPE: Wear suitable eye protection for the process. Flame-resistant clothing and leather gloves are good practice. (29 CFR 1926.353(e)(2))
6. Watch after the work stopsSmoldering fire starts after the crew leaves
  1. Administrative control: Where normal precautions are not enough, assign personnel to guard against fire during the work and for a sufficient time after it ends to make sure no fire can start. (29 CFR 1926.352(e))
  2. Administrative control: Under the general industry rule, keep the fire watch for at least a half hour after welding or cutting is completed. (29 CFR 1910.252(a)(2)(iii)(B))
  3. Administrative control: Walk adjacent rooms and concealed spaces, including the opposite side of walls. (29 CFR 1926.352(f))
  4. Administrative control: Sign the permit closed only after the final check.
7. Close out and restore protectionFire protection left impaired
  1. Administrative control: Do not allow cutting or welding in a sprinklered building while sprinkler protection is impaired. Return any impaired protection to service before work resumes. (29 CFR 1910.252(a)(2)(vi)(B))
  2. Administrative control: Keep hoses, cables and other equipment clear of passageways, ladders and stairs, and collect them when the work is done. (29 CFR 1926.350(f)(7))

Required PPE

What the standard says

  • The authorizing person must inspect the area before cutting or welding, and should set the precautions, preferably in a written permit. (29 CFR 1910.252(a)(2)(iv))

    “Before cutting or welding is permitted, the area shall be inspected by the individual responsible for authorizing cutting and welding operations.”
  • Relocate combustibles at least 35 feet from the work where practicable. (29 CFR 1910.252(a)(2)(vii))

    “Where practicable, all combustibles shall be relocated at least 35 feet (10.7 m) from the work site.”
  • Fire watchers are required where other than a minor fire might develop. (29 CFR 1910.252(a)(2)(iii)(A))

    “Fire watchers shall be required whenever welding or cutting is performed in locations where other than a minor fire might develop,”
  • Fire extinguishing equipment must be ready. (29 CFR 1926.352(d))

    “Suitable fire extinguishing equipment shall be immediately available in the work area and shall be maintained in a state of readiness for instant use.”
  • Do not weld where flammable paints or compounds create a hazard. (29 CFR 1926.352(c))

    “No welding, cutting, or heating shall be done where the application of flammable paints, or the presence of other flammable compounds, or heavy dust concentrations creates a hazard.”
  • Assign extra personnel as fire guards where normal precautions are not enough. (29 CFR 1926.352(e))

    “When the welding, cutting, or heating operation is such that normal fire prevention precautions are not sufficient, additional personnel shall be assigned to guard against fire while the actual welding, cutting, or heating operation is being performed”
  • Take the same precautions on the opposite side of walls and floors. (29 CFR 1926.352(f))

    “When welding, cutting, or heating is performed on walls, floors, and ceilings, since direct penetration of sparks or heat transfer may introduce a fire hazard to an adjacent area, the same precautions shall be taken on the opposite side”

Training

Management must insist that cutters, welders and their supervisors are suitably trained in the safe operation of equipment and the safe use of the process (29 CFR 1910.252(a)(2)(xiii)(C)). Fire watchers must be trained in the use of fire extinguishing equipment (29 CFR 1910.252(a)(2)(iii)(B)).

Frequently asked questions

Does OSHA require a JHA for hot work?
OSHA does not require a written JHA for hot work. The general industry welding standard says the authorizing person shall designate precautions, preferably in a written permit (29 CFR 1910.252(a)(2)(iv)). Many sites require a permit and a JHA anyway.
What goes in a hot work JHA?
List permit and area walk, clearing combustibles, fire watch placement, the work, the post-work watch and close-out. Add the authorizing person, the fire watcher and the extinguisher type.
How far must combustibles be moved from hot work?
Where practicable, combustibles must be moved at least 35 feet from the work site. Where they cannot be moved, shield them with flameproofed covers or metal guards or curtains (29 CFR 1910.252(a)(2)(vii)).

Related toolbox talks

PRINT AND EDIT

JHA template pack, $29

All 20 task templates as editable Word and Excel files and as PDF, in English and Spanish, plus a blank master form. Change them for your site and your equipment and use them inside your company.

  • 20 task JHA templates, editable Word (DOCX)
  • The same 20 as Excel (XLSX) and PDF
  • English and Spanish versions
  • A blank master JHA form
  • Hazards, ranked controls, PPE and the OSHA paragraphs for each task

Instant download. 30-day refund, no questions.