FREE JHA TEMPLATE
Electrical panel work job hazard analysis (JHA) template
Opening a panel puts a worker within reach of live parts, so shock, burns and arc blast are the main hazards. OSHA requires live parts to be deenergized before an employee works on or near them, unless that creates greater hazard or is infeasible (29 CFR 1910.333(a)(1)). Plan to de-energize, lock out and test first.
The task
Working in a distribution panel or breaker enclosure to add, replace or troubleshoot a circuit, including shutdown, testing, the work and re-energizing.
Steps, hazards and controls
Controls run from most effective to least. A citation beside a control means an OSHA paragraph requires it; with no citation it is good practice.
| Step | Hazard | Controls |
|---|---|---|
| 1. Plan the job and decide to de-energize | Choosing to work live when it is not necessary |
|
| 2. Notify people and locate the sources | A source is missed or someone re-energizes the panel |
|
| 3. Turn off, lock out and tag | Panel is turned back on while you are working |
|
| 4. Release stored energy and verify dead | Capacitors or backfeed leave parts live |
|
| 5. Open the panel and work | Contact with energized neighboring parts |
|
| 6. Energized work, only if de-energizing is not feasible | Shock or arc blast during live work |
|
| 7. Restore power in the right order | Re-energizing on top of someone or a leftover tool |
|
| 8. Close up and record the work | Panel left open or unmarked |
|
Required PPE
- Safety glasses
- Insulated, rated gloves
- Non-conductive footwear
- Hard hat, class E
- Arc-rated clothing and face shield for energized work
What the standard says
Deenergize live parts before working on or near them. (29 CFR 1910.333(a)(1))
“Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards”
Place a lock and a tag on each disconnecting means. (29 CFR 1910.333(b)(2)(iii)(A))
“A lock and a tag shall be placed on each disconnecting means used to deenergize circuits and equipment on which work is to be performed”
A qualified person must test that circuits are deenergized. (29 CFR 1910.333(b)(2)(iv)(B))
“A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized.”
Only qualified persons may work on energized equipment. (29 CFR 1910.333(c)(2))
“Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section.”
Construction: deenergized equipment must be rendered inoperative and tagged. (29 CFR 1926.417(b))
“Equipment and circuits. Equipment or circuits that are deenergized shall be rendered inoperative and shall have tags attached at all points where such equipment or circuits can be energized.”
Do not work close enough to a power circuit to contact it unless protected. (29 CFR 1926.416(a)(1))
“No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected”
Verify that everyone is clear before reenergizing. (29 CFR 1910.333(b)(2)(v)(D))
“There shall be a visual determination that all employees are clear of the circuits and equipment.”
Training
Employees who face a risk of electric shock that is not reduced to a safe level must be trained in the electrical safety-related work practices that pertain to their jobs (29 CFR 1910.332(a) and (b)(1)). Qualified persons must also be trained to distinguish exposed live parts and to determine nominal voltage (29 CFR 1910.332(b)(3)).
Frequently asked questions
- Does OSHA require a JHA for electrical panel work?
- OSHA does not require a written JHA for panel work. It does require deenergizing, locks and tags, testing and training under 29 CFR 1910.333 and 29 CFR 1910.332, and on construction sites under 29 CFR 1926.416 and 29 CFR 1926.417. This template does not cite NFPA 70E because it is not part of the cached OSHA text; use your company program for arc flash.
- What goes in a typical electrical panel work JHA?
- Include planning, shutdown, lock and tag, stored energy and testing, the work, any energized work, restoring power and close-out. Add the qualified person, the lock owner and the panel ID.
- Who can test whether a panel is dead?
- A qualified person must use test equipment to verify that the circuit elements and parts are deenergized, and must also verify that the equipment cannot be restarted (29 CFR 1910.333(b)(2)(iv)(A) and (B)).
Related toolbox talks
- Electrical safety: the free talk and the training kit
- Lockout/tagout (LOTO): the free talk and the training kit
- Extension cord safety: the free talk and the training kit
PRINT AND EDIT
JHA template pack, $29
All 20 task templates as editable Word and Excel files and as PDF, in English and Spanish, plus a blank master form. Change them for your site and your equipment and use them inside your company.
- 20 task JHA templates, editable Word (DOCX)
- The same 20 as Excel (XLSX) and PDF
- English and Spanish versions
- A blank master JHA form
- Hazards, ranked controls, PPE and the OSHA paragraphs for each task
Instant download. 30-day refund, no questions.