Construction (29 CFR 1926) · Subpart K: Electrical
OSHA 1926.441: Batteries and battery charging
29 CFR 1926.441 is titled "Batteries and battery charging". It is part of Subpart K (Electrical) of the construction standards.
It has no paragraph that is mainly about training, but our talks cite it for what it requires on the job.
Official source: eCFR, 29 CFR 1926.441
TRAINING
Training requirements
This section has no paragraph that is mainly about training. It is listed here because our toolbox talks cite it.
TALKS
Toolbox talks and kits for this standard
Talks for this standard are being written now. Request a kit for this standard.
OFFICIAL TEXT
Full text: 29 CFR 1926.441
Official text of the federal regulation (public domain). Training paragraphs are shaded.
(a) General requirements. (1) Batteries of the unsealed type shall be located in enclosures with outside vents or in well ventilated rooms and shall be arranged so as to prevent the escape of fumes, gases, or electrolyte spray into other areas.
(2) Ventilation shall be provided to ensure diffusion of the gases from the battery and to prevent the accumulation of an explosive mixture.
(3) Racks and trays shall be substantial and shall be treated to make them resistant to the electrolyte.
(4) Floors shall be of acid resistant construction unless protected from acid accumulations.
(5) Face shields, aprons, and rubber gloves shall be provided for workers handling acids or batteries.
(6) Facilities for quick drenching of the eyes and body shall be provided within 25 feet (7.62 m) of battery handling areas.
(7) Facilities shall be provided for flushing and neutralizing spilled electrolyte and for fire protection.
(b) Charging. (1) Battery charging installations shall be located in areas designated for that purpose.
(2) Charging apparatus shall be protected from damage by trucks.
(3) When batteries are being charged, the vent caps shall be kept in place to avoid electrolyte spray. Vent caps shall be maintained in functioning condition.